IECC 2015 Code Summary

 

CODE SECTION CODE REQUIREMENTS SUMMARY
C405.2 Lighting
controls
(Mandatory)
Lighting systems shall be provided with controls as specified in Sections C405.2.1, C405.2.2, C405.2.3, C405.2.4 and C405.2.5.
Exceptions: Lighting controls are not required for the following:
1. Areas designated as security or emergency areas that arerequired to be continuously lighted.
2. Interior exit stairways, interior exit ramps and exit passageways.
3. Emergency egress lighting that is normally off.
With few exceptions, lighting controls are now required in all size buildings,
and in all areas of the building. Exceptions: Interior exit stairways, ramps, passageways, security areas required to be continuously lit, emergency egress that is normally off.
C405.2.1
Occupant Sensor
Controls
Occupant sensor controls shall be installed to control lights in the following space types:
Classrooms/lecture/training rooms, Conference / meeting / multipurpose rooms, Copy/print rooms, Lounges, Employee lunch and break rooms, Private offices, Restrooms, Storage rooms, Janitorial closets, Locker rooms, and other spaces 300 square feet or less that are enclosed by floor-to-ceiling height partitions, Warehouses.
Areas required to have occupancy
sensor control have been greatly
expanded.
C405.2.1.1
Occupant sensor
control function.
Occupant sensor controls in spaces other than warehouses specified in Section C405.2.1 shall comply with the following:
· Automatically turn off lights within 30 minutes of all occupants leaving the space.
· Be manual on or controlled to automatically turn the lighting on to not more than 50 percent power.
· Shall incorporate a manual control to allow occupants to turn lights off.
With a few exceptions, occupancy
sensor control shall be vacancy, or half occupancy, and must include a manual control to turn lights off. Exceptions: Automatic on permitted to control public corridors, stairways, restrooms, primary entrance and lobbies, and areas where manual on would endanger safety or security of occupants.
C405.2.1.2
Occupant sensor
control function in
warehouses.
In warehouses, the lighting in aisle ways and open areas shall be controlled with occupant sensors that automatically reduce lighting power by not less than 50 percent when the areas are unoccupied. The occupant sensors shall control lighting in each aisle way independently and shall not control lighting beyond the aisle way being controlled by the sensor.
Warehouses are now required to use
occupancy sensors, and may not control more than one aisle. Lights must be able to reduce power by at least 50% when unoccupied.
C405.2.2 Timeswitch
controls
Each area of the building that is not provided with occupant sensor controls shall be provided with time switch controls.
With few exceptions all areas not
covered by occupancy controls will
include time based controls with manual override, 2 hour max override, and controlling not more than 5000 square feet.
C405.2.2.2 Light-reduction
controls
Spaces required to have light-reduction controls shall have a manual control that allows the occupant to reduce the connected lighting load in a reasonably uniform illumination pattern by at least 50 percent.
Light reduction may be achieved by
dimming, lamp switching, or fixture
control as long as it is done in a
reasonably uniform illumination pattern.
C405.2.3 Daylight-responsive
controls
Daylight-responsive controls shall be provided to control the electric lights within daylight zones in the following spaces:
• Spaces with a total of more than 150 watts of general
lighting within sidelight daylight zones.
• Spaces with a total of more than 150 watts of general
lighting within top light daylight zones.
Daylight responsive controls are not required for the following:
• Spaces in health care facilities where patient care is directly provided.
• Dwelling units and sleeping units.
• Lighting that is required to have specific application
control.
• Sidelight daylight zones on the first floor above grade in Group A-2 and Group M occupancies.
With few exceptions, daylight
responsive controls are required in all
spaces with more than 150 watts of
general lighting within their daylight
zones. Daylight zones are now defined
as two feet on either side of window,
and window head height into the space.
(floor to the top of the fenestration)
C405.2.3.1
Daylight-responsive
control
function
Where required, daylight-responsive controls shall be provided within each space for control of lights in that space and shall comply with all of the following:
• Lights in top light daylight shall be controlled
independently of lights in sidelight daylight zones.
• Daylight responsive controls within each space shall be configured so that they can be calibrated from within that space by authorized personnel.
• Calibration mechanisms shall be readily accessible.
• Where located in offices, classrooms, laboratories and library reading rooms, daylight responsive controls shall dim lights continuously from full light output to 15 percent of full light output or lower.
• Daylight responsive controls shall be capable of a
complete shutoff of all controlled lights.
Spaces requiring daylight responsive
controls will require a photo sensor that
can be adjusted from within the space,
can be calibrated from the floor, and in
classrooms and offices must allow for
dimming to at least 15%. In other spaces
the sensor must at a minimum be able
to turn the lights off in response to
daylight.
C405.2.5 Exterior
lighting controls
Lighting for exterior applications other than emergency lighting that is intended to be automatically off during building operation, lighting specifically required to meet health and life safety requirements or decorative gas lighting systems shall:
• Be provided with a control that automatically turns off the lighting as a function of available daylight.
• Where lighting the building façade or landscape, the lighting shall have controls that automatically shut off the lighting as a function of dawn/dusk and a set
opening and closing time.
• Where not covered in Item 2, the lighting shall have controls configured to automatically reduce the connected lighting power by not less than 30 percent from not later than midnight to 6 a.m., from one hour after business closing to one hour before business opening or during any period when activity has not been detected for a time of longer than 15 minutes.
Façade and landscape lighting must have
its own schedule and also incorporate a
photo sensor. All other lighting (with a
few exceptions) must be able to reduce
its connected load by 30% either based
on a schedule or on occupancy.
Exceptions: Lighting for covered vehicle entrances or exits from buildings or parking structures where required for safety, security or eye adaptation.
C406 Additional
efficiency package
options
Buildings shall comply with at least one of the following:
• More efficient HVAC performance.
• Reduced lighting power density
• Enhanced lighting controls
• On-site supply of renewable energy
• Provision of a dedicated outdoor air system for certain HVAC equipment
• High-efficiency service water heating
One must be chosen. Enhanced controls
includes dimming in all fixtures,
individual fixture control, a digital
control system with programmable
sensors, keypads, user control of
overhead lighting in open offices, and
load shedding.

 

LOGO_-_ALA_-_20151013Architectural Lighting Alliance

Dallas | Lubbock | Shreveport

Dallas Phone: 214.658.9000
Dallas Fax: 214.658.9002

Dallas Phone: 214.658.9000
Dallas Fax: 214.658.9002

Lubbock: 806-796-1322
Lubbock Fax: 806-796-1323

Shreveport: 318-674-2713
Shrev. Fax: 318-674-2741

© 2017 Architectural Lighting Alliance. All Rights Reserved.

Site designed and developed by americaneagle.com

close (X)